TO: HONORABLE CHAIRPERSON AND MEMBERS OF THE AZUSA UTILITY
BOARD
FROM: GEORGE F. MORROW, DIRECTOR OF UTILITIES
DATE: SEPTEMBER 22,2014
SUBJECT: 2013 ANNUAL SUMMARY INSPECTION REPORTS (GO 165 AND 174)
Azusa Light & Water is a municipal public utility designated as a Reliable Public Power
Provider under the American Public Power Association - RP3 Program. The Electric Division of
the Azusa Light&Water performs annual inspections of the City's electric facilities as part of its
commitment to promote a safe electric system and provide reliable electricity to City residents or
customers.
The 2013 annual inspections were performed in conformance with established minimum
inspections requirements adopted by the State of California Public Utilities Commission under
General Order 165 and 174. These inspections consist of, but not limited to, circuit and
streetlight patrols, infrared inspections, visual inspections of electrical equipment both overhead
and underground, intrusive and/or detailed wood pole inspections, and inspection of substation
facilities.
The 2013 Annual Inspection Report, which is a summary of the completed inspection program,
is hereby presented to the Azusa Utility Board in faithful compliance to applicable provision of
General Order 165 and 174. A copy of the completed inspection program summary is attached to
this report for reference and is also available online at the Utility's website address.
Prepared by: Dan Kjar—Electric Distribution Supervisor
F. Langit Jr.—Assistant Director of Electric Operations
Attachments:
1. GO 165 2013 Annual Report
2. GO 165 2013 Inspection Report
3. GO 174 2013 Annual Report
UB-141
AZUSA LIGHT & WATER DEPARTMENT
ANNUAL REPORT OF 2013
PURSUANT TO GENERAL ORDER NO. 165
Dated: 12/24/2013
UB-142
Azusa Light & Water Annual Compliance Report
to General Order No. 165
TABLE OF CONTENTS
Section Title Page
I. INTRODUCTION AND SUMMARY ,,.1
II. BACKGROUND .1
III. SUMMARY OF AZUSA LIGHT & WATER'S INSPECTIONS
AND CORRECTIVE ACTION ACTIVITIES DURING
CALENDAR YEAR 2013 3
A. Patrols 3
1. Circuit Patrols 3
2. Streetlight Patrols 3
B. Intrusive and Detailed Inspections .4
1. Intrusive Wood Pole Inspections 4
2. Overhead Detailed Inspections ,,..4
3. Underground and Pad Mounted Equipment
Detailed Inspections 5
C. Condition Ratings 5
UB-143
AZUSA LIGHT & WATER DEPARTMENT'S ANNUAL REPORT
PURSUANT TO GENERAL ORDER NO. 165
I.
INTRODUCTION AND SUMMARY
In 2013, Azusa completed 20 circuit patrols, 372 detailed inspections,
0 intrusive wood pole inspections, and 140 corrective actions on facilities
subject to G.O. 165. This report includes Attachment A, a table containing
summary data of Azusa's compliance activities for 2013 presented on a
system wide basis.
II.
BACKGROUND
The California Public Utility Commission adopted G.O. 165, which
established minimum inspection requirements for certain electric distribution
facilities (including maximum allowable inspection cycle lengths), condition
rating, and recordkeeping and reporting on scheduling and performance of
corrective action. G.O. 165 imposed the following reporting requirements:
Each utility shall complete an annual report detailing its compliance with the
general order. These reports will include the utility's plans for the types of
inspections and equipment to be inspected during the coming year. The
report shall identify the number of facilities, by type, which have been
UB-144
inspected during the previous period. It shall identify those facilities which
were scheduled for inspection but which were not inspected according to
schedule and shall explain why the inspections were not conducted, and a
date certain by which the required inspection will occur. The report shall
also present the total and percentage breakdown of equipment rated at each
condition rating level, including that equipment determined to be in need of
corrective action. Where corrective action was scheduled during the
reporting period, the report will present the total and percentage of
equipment which was and was not corrected during the reporting period. For
the latter, an explanation will be provided, including a date certain by which
required corrective action will occur. The report will also present totals and
the percentage of equipment in need of corrective action, but with a schedule
date beyond the reporting period, classified by the amount of time remaining
before the scheduled action. All of the above required information shall be
presented for each type of identified facility.
UB-1245
III.
SUMMARY OF AZUSA LIGHT & WATER'S INSPECTIONS
AND CORRECTIVE ACTION ACTIVITIES DURING
CALENDAR YEAR 2013
G.O. 165 requires annual inspection performance data, condition
ratings, and corrective action information. The following is a narrative
summary of the required data. In addition, Attachment A contains a tabular
summary of data.
A. Patrols
As defined in G.O. 165, a patrol is a simple visual inspection, of
applicable utility equipment and structures that is designed to identify
obvious structural problems and hazards. Patrols may be carried out in the
course of other company business.
1. Circuit Patrols
G.O. 165 requires annual patrols of all urban circuits. In 2013 Azusa
completed 20 circuits, or 100 % of the planned number of circuit patrols due
for inspection in 2013.
2. Streetlight Patrols
G.O. 165 requires annual patrols of all urban streetlights. In 2013,
Azusa patrolled 100 % of its urban streetlight inventory.
UB-t46
B. Intrusive and Detailed Inspections
1. Intrusive Wood Pole Inspections
In 2012, Azusa planned to complete a total of 0 intrusive inspections
of wood poles in 2013. Azusa completed 100% of the planned inspections
from 2001 to 2004. Overall, our G.O. 165 compliance plan is completed
given that all poles older than 10 years have received their first intrusive
inspection. A total of 2,845 poles were tested.
2. Overhead Detailed Inspections
In 2013, Azusa planned inspections of 191 overhead transformer
detailed inspections and completed 191 detailed inspections or 20% of total
overhead transformers on the system. For overhead switching and protective
devices, the 2013 plan was to complete 20 detailed inspections. Azusa
completed 20 detailed inspections or 20% of the planned five year program.
For overhead capacitors, Azusa planned and completed 5 detailed
inspections, 20% of the five year plan. Azusa also completed detailed
inspections on all of the overhead conductors. Azusa completed inspections
on 88.8 miles of overhead conductor or 100 % of the planned inspections in
2013.
3. Underground and Pad Mounted Equipment Detailed
Inspections
UB-147
In 2013, Azusa planned to complete 148 underground and pad
mounted equipment detailed inspections. Azusa actually completed 155
underground and pad mounted equipment detailed inspections. This amounts
to 33% of Underground and 20% of Padmount system devices.
C. Condition Ratings
G.O. 165 requires Azusa to rate the condition of specified equipment such
as, (transformers, switches, regulators, capacitors and conductors). Under
Azusa's condition rating system, established in 2001, revised in 2004,
condition rated 1 equipment and structure repairs are made immediately.
Azusa plans ahead for condition rated 2 &3 repairs. Condition rating 4 is
used for all equipment whose condition either does not require any repair or
does not require any scheduled repair. As of 12/24/2013, Azusa's condition
rating system included 0 facilities with Level 1 condition ratings, 0 facilities
with Level 2 condition ratings and 3 facilities with Level 3 condition ratings.
The remaining 369 facilities subject to condition rating were rated at Level
4.
UB-148
Summary of 2013 G.O. 165 Inspection Report
Transformers:
Pole mount: 191 inspected - 20%required for 5 yr. cycle
Circuits completed: Paramount
Pasadena
Rockvale
Todd
Arrow
Pad mount: 112 inspected—20%required for 5 yr. cycle
Circuits completed: Angeleno
Brewery
Cerritos
Coney
B.U.R.D: 34 inspected—33%required for 3 yr. cycle
Areas completed: Rue-DeValle& Sally Lee
100/200 Block E. Payson&Kirkwall
200 E. Gladstone
200 W. Arrow
1015 E. Arrow
Switches:
PME: 5 inspected- 20%required for 5 yr.cycle
Switches inspected: 316, 317, 318, 319, & 320
Vacuum: 4 inspected—33%required for 3 yr cycle
Switches completed: 401,402, 403 &404 (100%Inspected in 2013)
Pole mount: 20 inspected—20%required for 5 yr. cycle
Switches completed: 82, 83, 84, 5,26, 30, 69,4, 24, 29, 51, 54,73, 68,
13 , 70, 78, 105, 113, & 115
Capacitors:
Overhead 5 inspected—20%required for 5 yr. cycle
Capacitor Banks Completed: 13, 19,26, 27, &30
Pad Mount 0 inspected
Capacitor Banks Completed: 0
(28, 33, and 34 Insp. In 2012, 100%of 3 Yr. Plan)
UB-149
"ova
AZUSA
IGS 7 & NATER
For Quality of Life
AZUSA LIGHT & WATER
2013 ANNUAL REPORT
PURSUANT TO GENERAL ORDER NO. 174
Dated: 09/09/2014
UB-150
AZUSA LIGHT & WATER
2013 ANNUAL REPORT
GENERAL ORDER NO.174
TABLE OF CONTENTS
Section Title Page
I. INTRODUCTION ... 3
II. BACKGROUND .4
III. SUMMARY 4
IV. GO I74 INSPECTION REQUIREMENT .5
V. SAMPLE INSPECTION FORM 8
UB-151
AZUSA LIGHT & WATER
2013 ANNUAL REPORT - GENERAL ORDER NO.174
I. INTRODUCTION
Pursuant to General Order 174 and in compliance to the safety order,
Azusa Light & Water established in early 2013 a monthly schedule for
performing inspections inside City owned electrical substations/facilities.
Inspections are performed by designated qualified personnel of Azusa Light
& Water and their findings are recorded in a checklist format used during
these inspections. Azusa Light & Water currently owns and operate only
two (2) electrical substations in the City. Both of these substations are jointly
operated with another investor owned utility, which operates their own
portion of switching facilities inside these substations. For calendar year
2013, Azusa Light & Water followed an inspection program performed by
qualified personnel and the results were recorded and retained. Azusa
complied with GO 174 by completing monthly inspections of the two City
of Azusa owned electrical substations/facilities located within Azusa's
electric service territory. Based on the substation inspections, there were
two (2) URGENT ratings that were recorded which required immediate
corrective action. There were three (3) TIMELY ratings which require
UB-x'52
corrective action within 6 months, were recorded and duly corrected. There
was one (1) NON EMERGENCY rating, which requires corrective action in
two (2) years was recorded, and that the recommended correction is pending
in this one substation which is subject to G.O. 174.
IL BACKGROUND
The California Public Utility Commission adopted G.O. 174, which
established inspection and reporting requirements for electric substations.
These requirements are set forth under Section 3 and Section 4 of the GO
174 as adopted on 25 October 2012 under CPUC Decision 12-10-029. A
copy of the GO 174 is included in this report for reference.
IIh SUMMARY OF INSPECTIONS AND CORRECTIVE
ACTION ACTIVITIES DURING CALENDAR YEAR 2013
G.O. 174 requires the governing utility to identify, set a condition
rating standard (where applicable), and categorize the inspection for all
distribution substation within the utility's jurisdiction. The condition ratings
and time for corrective action was established by Azusa Light & Water for
performing inspection and assessment on the condition of specified
substation equipment such as, (transformers, switches, regulators, capacitors,
relays, batteries, A/C units and conductors etc.). Under Azusa's condition
UB-1453
rating system, a condition rated "Level 1" requires equipment and structure
repairs are performed or made immediately. Azusa plans ahead for needed
repairs under conditions rated "Levels 2" & "3". Condition rating "Level 4"
is used for all equipment whose condition either does not require any repair
or does not require any scheduled repair.
As of 12/24/ 2013 and after completing the monthly scheduled
inspection for the reporting period, Azusa's condition rating system included
two (2) facilities/equipment with Level 1 condition ratings. The blown cap
bank fuse at Kirkwall Substation was immediately replaced and also a DC
battery bank that showed imminent failure was immediately replaced with
new batteries. Also, three (3) identified facilities/equipment with Level 2
condition ratings, were all corrected. These corrections included replacement
of control relay for cap bank at Kirkwall Substation, installation of bird
guard at Azusa Substation CB bushings, and restoration of internal telephone
extension line in the control room at Azusa Substation. There was one (1)
facility/equipment with Level 3 condition rating which entailed replacement
of one of the security camera lens at Kirkwall Sub. All other remaining
facilities subject to condition rating were rated at Level 4.
IV. GO 174
UB-f54
General Order 174
Rules for Electric Utility Substations
(Adopted October 25, 2012 by Decision 12-10-029)
Inspection Programs
30 General
30.1 Each Operator shall establish, update as needed, and follow an
Inspection Program. At a minimum, this Program shall specify for each
piece of equipment and system listed in Rule 32.1:
❑ Inspection activities
❑ Frequency of Inspections
❑ Record keeping and retention
30.2 Inspections shall be performed by persons who, by reason of training,
experience and instruction, are qualified to perform the task.
31 Frequency
31.1 Substations shall be inspected as frequently as necessary.
❑ Time intervals or other bases shall be specified in the Inspection
Program.
32 Facilities
32.1 Facilities subject to Inspection shall include, but are not limited to:
❑ Batteries
❑ Buses
❑ Support Structures
❑ Capacitor Banks
❑ Circuit Breakers
❑ Fire Detection and Suppression System (Where applicable)
O Grounding System
❑ Insulators/Bushing/Arrestors
O Perimeter Fences and Gates
❑ Transformers
❑ Reactors
❑ Voltage Regulators
UB-155
33 Records
33.1 Electronic or hard copy records of completed Inspections shall
include, at a minimum:
❑ Inspector name or identification
❑ Inspection date
❑ Brief description of identified discrepancies
❑ Condition rating (where applicable)
❑ Scheduled date of corrective action (where applicable)
33.2 Electronic or hard copy records of completed Inspections shall be
retained for not less than five (5) years.
Section IV
Reporting
40 Annual Filings
40.1 No later than July 1st of each year, each Operator shall transmit to the
Utilities Safety and Reliability Branch (USRB) an Inspection Program
Summary.
Changes to the Inspection Program shall be reflected in the Inspection
Program Summary, including the effective date of the change. Should no
changes occur since the previous filing, the Operator shall transmit written
correspondence confirming that no changes were made to the program.
40.2 No later than July 1st of each year, each Operator shall transmit to the
CPSD a report summarizing completed and past due Inspections for the
prior calendar year.
UB-156
V. SAMPLE INSPECTION FORM
Substation Inspection Form
Substation:
Date: Inpector: Ratin•s Res•onse Time
Requires urgent or immediate
1 corrective action 1 -9 days
•
2 ' Requires-timelycorrective action 6 months
3 No emergency repair action 2 years
Good condition no action
4 required
0 Not A.•licatable
EXPLAIN ALL
1,2, &3s
Area Rate Description
Perimeter Fences &Gates
Circuit Switcher(s)
Transformers/LTCs
Insulators/Bushings
Support Structure
Grounding System
VCB/OCBICap Banks
Cameras
Fire Suppresion
Vandalism/Graffiti/Tampering
Signage
Control House/Storage Bin
Landscaping/Refuse/Weeds
Batteries
Pilot Cell Voltage
NOTES: